| RDW8 | HU | 25 | 16 | 3 | H | Ladenivo | AC230V | Gjin ûnderspanning |
| Produktkoade | Brekkende klasse | Frame-stroom | Nominale stroom | Oantal peallen | Kontrôler | Ynstallaasjemodus | Kontrôlespanning | Bylagen |
| Hege spanning yntelligint Universele stroombrekker | HU | 25:2500(06-25) 40:4000(08-40) 63:6300(40-63) | 06:630 oere 08:800 oere 10:1000A 12:1250A 16:1600 oere 20:2000A 25:2500A 29:2900A 32:3200A 36:3600A 40:4000A 50:5000A 60:6000A | 3:3P 4:4P | M: Standert type (digitaal display) R: Ferbettere type (Liquid crystal Display) H: Avansearre type (LCD mei kommunikaasje) | Ladenivo Lade fertikaal Fêst nivo Fêste fertikale | AC230V AC400V DC220V DC110V | Ynterfase-partysje Fjouwerfâldige transformaasje Doarframe Gjin ûnderspanning Underspanning direkt Under kalandertiid Mechanyske ynterfergrendeling Mechanyske ynterfergrendeling Ien slot, ien kaai Twa slûzen en ien kaai Trije slûzen, twa kaaien It is 50-50 Seis oan, seis oereff |
● RDW8HU standertkonfiguraasje: shunt, sluting, elektryske operaasje, 4-groepkonverzje, doarframe, ynterfazeskieding
● Bygelyks: jo moatte in RDW8HU-2500 bestelle, trijepolige lade, nominale stroom 1250A, yntelliginte controller foar R-type, kontrôlespanning AC230V
● Útdrukt as: RDW8HU-25 12/3R ladenivo AC230V sûnder ûnderspanning.
Normale wurkomstannichheden
■ De omjouwingstemperatuer is -5℃ ~ +40℃, en de gemiddelde wearde fan 24 oeren is net heger as +35°C;
Noat:As de boppeste limyt +40 ℃ grutter is of de ûnderste limyt leger is as -5 ℃, moat de brûker ûnderhannelje mei de fabrikant.
■ De hichte fan it ynstallaasjeplak is net mear as 2000m;
Noat:Rieplachtsje de fabrikant foar de stroomûnderbrekker dy't brûkt wurdt yn 'e wurkomjouwing mei in hichte fan mear as 2000m.
■ De relative fochtigens fan 'e atmosfear is net mear as 50% as de omjouwingstemperatuer +40℃ is; it kin in hegere relative fochtigens hawwe by legere temperatueren. Bygelyks, de wietste moanne hat in gemiddelde maksimale relative fochtigens fan 90%, wylst de gemiddelde minimumtemperatuer fan 'e moanne +20℃ is, en behannelingsmaatregels moatte wurde nommen foar de sa no en dan kondensaasje troch temperatuerferoarings.
■ It fersmoargingsnivo is 3;
■ As de nominale wurkspanning fan it haadsirkwy AC 800V ~ AC1140V is, moatte it kontrôlesirkwy en it helpsirkwy mei in transformator fan it haadsirkwy isolearre wurde, en de maksimale wurkspanning fan it kontrôlesirkwy en it helpsirkwy is AC400V, de ynstallaasjekategory fan it kontrôlesirkwy en it helpsirkwy is Ⅲ;
■De stroombrekker is geskikt foar elektromagnetyske omjouwing A;
■Brûk kategory B.
Normale ynstallaasjebetingsten
■ Ynstallearjen fan fêste stroomûnderbrekker: De stroomûnderbrekker wurdt yn 'e distribúsjekast pleatst en befeilige mei M10 (mear as 2500A skelframe) bouten en ringen.
De stroombrekker wurdt soepel ynstalleare sûnder ekstra meganyske stress.Foarkom skea oan stroomûnderbrekkers of min kontakt fan 'e haadrail;
■ Ynstallearjen fan ladetype-breaker: Ferwiderje de stroombrekkerslichem fan 'e ladestoel, ynstallearje de ladestoel yn 'e distribúsjekabinet earst,en draai oan mei M10 (mear as 2500A shell frame) bouten en ringen. De montagenivo fan 'e stroombrekker is stabyl, der moat gjin ekstra meganyske stress wêze, om skea oan 'e stroombrekker of min kontakt tusken de haadbus en de te foarkommen.sekundêr sirkwy,nei de foltôging fan it lichem fan 'e stroomûnderbrekker yn' e ferbiningsposysje fan 'e ladestoel;
■De stroombrekker moat ynstalleare wurde op in plak sûnder eksploazjerisiko en geliedend stof, sûnder genôch om metaal te korrodearjen enferneatigje isolaasje;
■It beskermingsnivo is IP20, As de stroomûnderbrekker yn 'e kast ynstalleare is en it doarframe ynstalleare is, kin it beskermingsnivoIP40 berikke.
Normale opslach- en transportbetingsten
■ De ûnderste temperatuergrins is net leger as -25℃, de boppegrins is net mear as +55℃; Relative fochtigens (+25℃) is net heger95%;
■It produkt moat foarsichtich behannele wurde tidens it ferfier, en moat net omkeard wurde om gewelddiedige botsingen te foarkommen.
| Oantal peallen (Tabel 1) | 3P/4P | ||||||||
| Frekwinsje | 50/60Hz | ||||||||
| Nominale wurkspanning Ue (V) | AC800V/AC1000V/AC1140V | ||||||||
| Rated ympuls wjerstân spanning Uimp (kV) | AC12kV | ||||||||
| Nominale isolaasjespanning Ui (V) | AC1250V | ||||||||
| Frameklasse | 25HU | 40HU | 63HU | ||||||
| Yn (A) | |||||||||
| 630 | ● | ||||||||
| 800 | ● | ● | |||||||
| 1000 | ● | ● | |||||||
| 1250 | ● | ● | |||||||
| 1600 | ● | ● | |||||||
| 2000 | ● | ● | |||||||
| 2500 | ● | ● | |||||||
| 2900 | ● | ||||||||
| 3200 | ● | ||||||||
| 3600 | ● | ||||||||
| 4000 | ● | ● | |||||||
| 5000 | ● | ||||||||
| 6300 | ● | ||||||||
| Breekkapasiteit (AC800V) | AC800V | AC1000V | AC1140V | AC800V | AC1000V | AC1140V | AC800V | AC1000V | AC1140V |
| Rated limyt koartsluting brekkende kapasiteit Icu (KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Nominale wurkingskapasiteit foar koartsluting Ics (KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Beoardiele koarte-termyn úthâldingsfermogen Icw/1s (KA) | 60 | 55 | 50 | 75 | 60 | 60 | 85 | 66 | 66 |
| Folsleine segminttiid (gjin ekstra fertraging) | 25~30ms | ||||||||
| Slutingstiid | ≤70ms | ||||||||
| Mechanyske libbensdoer (mei ûnderhâld) | 20000 | 20000 | 13000 | ||||||
| Mechanyske libbensdoer (gjin ûnderhâld) | 10000 | 10000 | 6500 | ||||||
| Elektryske libbensduur | 7000 | 6000 | 1500 | ||||||
| Ferbiningsmodus (horizontaal) | ● | ||||||||
| Ferbiningsmodus (fertikaal) | ● | ||||||||
| Ferbiningsmodus (boppe horizontaal en ûnder fertikaal) Ferbiningsmodus (fertikaal omheech en horizontaal omleech) | ● | ||||||||
Noat:De meganyske libbensdoer fan 'e ladestoel is 100 kear, fan "skieding" nei "ferbining" nei "skieding" is ien kear, en de operaasjesyklus is 1 kear / 2 min.
①Model fan yntelliginte kontrôler(oerienkommende produktmodel);
②LCD floeibere kristal displayfinsterkin elke fazestroomwearde, spanningswearde, ynstellingsparameter, foutstroom, stream, útskeakeltiid en ynformaasjefraachparameters werjaan;
③Overload lange fertraging flater oantsjutting;
④Koartsluting koarte fertraging ynverse tiidfoutyndikaasje;
⑤ Yndikaasje fan grûn- of nulleiderfout;
⑥Ynstellingstoets:Skakelje fluch nei it haadmenu fan it parameterynstellingsmenu, (yn 'e wachtwurdynfierynterface is de "Rjochts"-toets);
⑦Mjitkaai:Skakelje fluch nei it standert haadmenu foar mjitting, (ûnder de wachtwurdynfierynterface is de "Links"-toets);
⑧Omheech-toetsFerpleats de menu-ynhâld omheech op it hjoeddeiske nivo, of feroarje de seleksje omheech Parameters;
⑨Omleech toetsFerpleats menu-ynhâld nei ûnderen op it aktuele nivo, of feroarje de seleksje nei ûnderen Parameters;
⑩Tebektoets:Ferlaat it hjoeddeiske nivo om it menu op it boppeste nivo yn te gean, of annulearje de hjoeddeiske parameter de seleksje fan;
⑪Ok-toets:Fier it menu fan it folgjende nivo yn dêr't it aktuele item nei wiist, of gean troch nei de aktuele parameter Selektearje, bewarje de makke wizigingen;
⑫Fraachkaai:Wikselje nei it menu foar skiednis en ûnderhâldstema;
⑬ Ynstellingskaai foar beskermingsparameters:Wikselje nei it temamenu foar it ynstellen fan beskermingsparameters;
⑭ Yndikaasje fan direkte koartslutingfout;
⑮ Yndikaasje foar koartsluting mei koarte fertraging mei fêste tiid;
⑯Kommunikaasje-yndikaasje:
Profibus: gjin kommunikaasje as út, kommunikaasje konstant ljocht;
Modbus: skeakelt út as der gjin kommunikaasje beskikber is en knippert as der kommunikaasje beskikber is.
⑰Normale oantsjutting:yn 'e krêftstatus is de wurkstatus normaal, de LED knippert altyd grien;
⑱Fout-/alarmindikaat:de "fout/alarm" LED ljochtet net op tidens normale operaasje; by storing by útskeakeljen is de "Fout/alarm" LED read en knippert rap; yn gefal fan alarm as de LED konstant helder read is;
⑲Reset-knopAs de yntelliginte controller yn 'e fout-/alarmsteat is, moat er werom nei de normale wurksteat. Druk op dizze toets om de fout-/alarmindikaasje fan 'e yntelliginte controller te wiskjen.
| Ynstelde wearde Ir fan 'e aksjestroom (Tabel 2) | (0.4~1.0) Yn+ÚT | Hjoeddeiske tolerânsje | ±10% | ||||||||||||||
| Tapaste stroom I | Stel in reistiid yn | ||||||||||||||||
| 1.05Ir | >2o giet net troch | ||||||||||||||||
| 1.3Ir | < 1 oere reis | ||||||||||||||||
| Type beskermingskarakteristiken | Foutstroom | Stel tiid yn Tr (s) | |||||||||||||||
| SI Standert inverse tiid | 1.5Ir | 0.61 | 0.98 | 1.47 | 2.46 | 3.68 | 4.91 | 6.14 | 9.21 | 11.05 | 17.19 | 24.56 | 36.84 | 49.13 | 61.41 | 73.69 | 85.97 |
| 2Ir | 0.36 | 0.57 | 0.86 | 1.43 | 2.15 | 2.87 | 3.58 | 5.37 | 6.45 | 10.03 | 14.33 | 21.49 | 28.65 | 35.82 | 42.98 | 50.15 | |
| 6Ir | 0.14 | 0.22 | 0.33 | 0.55 | 0.82 | 1.1 | 1.37 | 2.06 | 2.47 | 3.84 | 5.48 | 8.22 | 10.96 | 13.7 | 16.45 | 19.19 | |
| 7.2Ir | 0.12 | 0.2 | 0.3 | 0.5 | 0.74 | 0.99 | 1.24 | 1.86 | 2.23 | 3.48 | 4.97 | 7.45 | 9.93 | 12.42 | 14.9 | 17.38 | |
| VI snelheid ynverse tiid | 1.5Ir | 2 | 3.2 | 4.8 | 8 | 12 | 16 | 20 | 27 | 36.6 | 56 | 80 | 120 | 160 | 200 | 240 | 280 |
| 2Ir | 1 | 1.6 | 2.4 | 4 | 6 | 8 | 10 | 13.5 | 18 | 28 | 40 | 60 | 80 | 100 | 120 | 140 | |
| 6Ir | 0.2 | 0.32 | 0.48 | 0.8 | 1.2 | 1.6 | 2 | 2.7 | 3.6 | 5.6 | 8 | 12 | 16 | 20 | 24 | 28 | |
| 7.2Ir | 0.16 | 0.26 | 0.39 | 0.65 | 0.97 | 1.29 | 1.61 | 2.18 | 2.9 | 4.52 | 6.45 | 9.68 | 12.9 | 16.13 | 19.35 | 22.58 | |
| EI(G) Express inverse tiid (Algemiene distribúsjebeskerming) | 1.5Ir | 8 | 12.8 | 19.2 | 32 | 48 | 64 | 80 | 108 | 144 | 224 | 320 | 480 | 640 | 800 | 960 | 1000 |
| 2Ir | 3.33 | 5.33 | 8 | 13.33 | 20 | 26.67 | 33.33 | 45 | 60 | 93.33 | 133.33 | 200 | 266.67 | 333.33 | 400 | 433.33 | |
| 6Ir | 0.29 | 0.46 | 0.69 | 1.14 | 1.71 | 2.29 | 2.86 | 3.86 | 5.14 | 8 | 11.43 | 17.14 | 22.86 | 28.57 | 34.29 | 37.14 | |
| 7.2Ir | 0.2 | 0.31 | 0.47 | 0.79 | 1.18 | 1.57 | 1.97 | 2.66 | 3.58 | 5.51 | 7.87 | 11.8 | 15.74 | 19.67 | 23.6 | 25.57 | |
| EI(M) Express inverse tiid (Motorbeskerming) | 1.5Ir | 6.22 | 9.96 | 14.93 | 24.89 | 37.34 | 49.78 | 62.23 | 84.01 | 112.01 | 174.24 | 248.91 | 373.37 | 497.82 | 622.28 | 746.73 | 208.96 |
| 2Ir | 2.95 | 4.72 | 7.07 | 11.79 | 17.69 | 23.58 | 29.48 | 39.79 | 53.06 | 82.53 | 117.9 | 176.86 | 235.81 | 294.76 | 353.71 | 383.19 | |
| 6Ir | 0.28 | 0.45 | 0.68 | 1.13 | 1.69 | 2.26 | 2.82 | 3.81 | 5.08 | 7.9 | 11.29 | 16.94 | 22.58 | 28.23 | 33.88 | 36.7 | |
| 7.2Ir | 0.2 | 0.31 | 0.47 | 0.78 | 1.17 | 1.56 | 1.95 | 2.63 | 3.51 | 5.46 | 7.8 | 11.7 | 15.61 | 19.51 | 23.41 | 25.56 | |
| Kompatibel mei HV Heechspanningsfuse | 1.5Ir | 2.46 | 3.94 | 5.91 | 9.85 | 14.77 | 19.69 | 24.62 | 33.23 | 44.31 | 68.92 | 98.46 | 147.69 | 196.92 | 246.15 | 295.38 | 320 |
| 2Ir | 0.67 | 1.07 | 1.6 | 2.67 | 4 | 5.33 | 6.67 | 9 | 12 | 18.67 | 26.67 | 40 | 53.33 | 66.67 | 80 | 86.67 | |
| 6Ir | 0.01 | 0.01 | 0.02 | 0.03 | 0.05 | 0.06 | 0.08 | 0.1 | 0.14 | 0.22 | 0.31 | 0.46 | 0.62 | 0.77 | 0.93 | 1 | |
| 7.2Ir | 0 | 0.01 | 0.01 | 0.01 | 0.02 | 0.03 | 0.04 | 0.05 | 0.07 | 0.1 | 0.15 | 0.22 | 0.3 | 0.37 | 0.45 | 0.48 | |
| I²T Universele ynverse tiidbeskerming | 1.5Ir | 15 | 30 | 60 | 120 | 240 | 360 | 480 | 600 | 720 | 840 | 960 | |||||
| 2Ir | 8.44 | 16.88 | 33.75 | 67.5 | 135 | 202.5 | 270 | 337.5 | 405 | 472.5 | 540 | ||||||
| 6Ir | 0.94 | 1.88 | 3.75 | 7.5 | 15 | 22.5 | 30 | 37.5 | 45 | 52.5 | 60 | ||||||
| 7.2Ir | 0.65 | 1.3 | 2.6 | 5.21 | 10.42 | 15.63 | 20.83 | 26.04 | 31.25 | 36.46 | 41.67 | ||||||
Noat:ikDe fabryksstandert fan 'e yntelliginte controller is universele omkearde tiidbeskerming foar lange fertraging: I2TL = (1.5Ir) 2t, tL - lange fertraging 1.5Ir ynstellingstiid, TL - aksjetiid foar lange fertraging, flater yn operaasjetiid ± 15%.
RDW8HU-2500/4000/6300 R-type sekundêr circuit bedradingsdiagram terminalfunksje en symboalynterpretaasje
| Terminalnûmer | Funksjebeskriuwing | Symboal | Parafrase | Opmerking |
| 1,2 | Hulpstroomynfier: AC230V, AC400V, DC220V, DC110V | RDW8HU | RDW8HU universele stroombrekker | |
| 3,4,5 | Hulpkontakt foar foutútskeakeling, kontaktkapasiteit: AC250V, 3A | S1~S4 | Sinjaallampe | Brûker oanlevere |
| 20 | Grûn (PE) | TA | Stroomtransformator | |
| 21, 22, 23, 24 | Spanningssignaalmjitting, 21 is ferbûn mei faze N, 22 is ferbûn mei faze A, 23 is ferbûn mei faze B, 24 is ferbûn mei faze C | SAL | mikroskakelaar | |
| 27,28 | Underspanningsfrijlitting | SB1 | Iepenknop | Brûker oanlevere |
| 29,30 | Shuntfrijlitting | SB2 | Slútknop | Brûker oanlevere |
| 31,32 | Slutende elektromagneet | X | Slutende elektromagneet | |
| 33,34,35 | Elektrysk bestjoeringsmeganisme (opslach fan elektryske enerzjy), 37 ferbûn mei griene line, 38 ferbûn mei swarte line, 39 ferbûn mei reade line | F | Shuntfrijlitting | |
| 36~48 | Hulpkontaktterminal | Q | Underspanningsfrijlitting | |
| ★Om't de haadspanning fan it sirkwy fan dizze searje hege spanning is, moat de spanningssignaalmjitting fan 'e R/H-type controller 21,22/23,24 ferbûn wurde mei de spanningskonverzjemodule. | M | Elektrysk bestjoeringsmeganisme | ||
| SA | Elektryske bestjoeringsmeganisme reisschakelaar | |||
| Fu | lont | Brûker oanlevere | ||
| PE | Grûndraad | |||
| N | Neutraal (N-faze) | |||
| A, B, C | Fazeline | |||
| AX | Hulpkontakt | |||
RDW8HU-2500/4000/6300 H-type sekundêr circuit bedradingsdiagram terminalfunksje en symboalynterpretaasje
| Terminalnûmer | Funksjebeskriuwing | Symboal | Parafrase | Opmerking |
| 1,2 | Hulpstroomynfier: AC230V, AC400V, DC220V, DC110V | RDW8HU | RDW8HU universele stroombrekker | |
| 3,4,5 | Hulpkontakt foar foutútskeakeling, kontaktkapasiteit: AC250V, 3A | S1~S4 | Sinjaallampe | Brûker oanlevere |
| 10,11 | Kommunikaasje-ynterface-útfier, 10 is (+), 11 is (-) (Opmerking: Standert Modbus-RTU-kommunikaasjemodus) | TA | Stroomtransformator | |
| 12~15 | DO1, programmeerbere sinjaalútfier, kontaktkapasiteit: AC250V, 3A | SAL | Mikroskeakel | |
| 14,15 | DO2DO3, iepeningssinjaalútfier, kontaktkapasiteit: AC250V, 3A | SB1 | Iepenknop | Brûker oanlevere |
| 16,17 | DO4, slútsignaalútfier, kontaktkapasiteit: AC250V, 3A | SB2 | Slútknop | Brûker oanlevere |
| 18,19 | Grûn (PE) | X | Slutende elektromagneet | |
| 20 | Spanningssignaalmjitting, 21 is ferbûn mei faze N, 22 is ferbûn mei faze A, 23 is ferbûn mei faze B, 24 is ferbûn mei faze C | F | Shuntfrijlitting | |
| 21, 22, 23, 24 | Eksterne N-transformatorynfier | Q | Underspanningsfrijlitting | |
| 25,26 | Underspanningsfrijlitting | M | Elektrysk bestjoeringsmeganisme | |
| 27,28 | Shuntfrijlitting | SA | Elektryske bestjoeringsmeganisme reisschakelaar | |
| 29,30 | Slutende elektromagneet | Fu | lont | Brûker oanlevere |
| 31,32 | Elektrysk bestjoeringsmeganisme (opslach fan elektryske enerzjy), 37 ferbûn mei griene line, 38 ferbûn mei swarte line, 39 ferbûn mei reade line | PE | Grûndraad | |
| 33,34,35 | Hulpkontaktterminal | N | Neutraal (N-faze) | |
| 36~48 | A, B, C | Fazeline | ||
| ★Om't de haadspanning fan it sirkwy fan dizze searje hege spanning is, moat de spanningssignaalmjitting fan 'e R/H-type controller 21,22/23,24 ferbûn wurde mei de spanningskonverzjemodule. | AX | Hulpkontakt | Selektive gearstalling | |
| ST-DP-module | Dizze parameter is fereaske as de kommunikaasjemodus Profibus-DP is | Selektive gearstalling | ||
| ST Power-module | Kommunikaasjefunksje as nedich | Selektive gearstalling | ||
| ST201 Relaismodule | Kommunikaasjefunksje as nedich | |||
RDW8HU-2500 Intelligente Universele Stroombrekker (Ladetype)
| Nominale stroom (A) | Raildikte H(mm) |
| 630, 800, 1000, 1250, 1600 | 15 |
| 2000,2500 | 20 |
RDW8HU-2500 De stroom komt oerien mei de dikte fan 'e busbar
RRDW8HU-2500 Intelligente Universele Stroombrekker (fêst)
| Nominale stroom (A) | Raildikte H(mm) |
| 630, 800, 1000, 1250, 1600 | 15 |
| 2000,2500 | 20 |
RDW8HU-2500 De stroom komt oerien mei de dikte fan 'e busbar
RDW8HU-4000 Intelligente Universele Stroombrekker (Ladetype)
| Nominale stroom (A) | Raildikte H(mm) |
| 800, 1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000 | 20 |
De stroom komt oerien mei de dikte fan 'e busbar
RDW8HU-4000 Intelligente Universele Stroombrekker (fêst)
| Nominale stroom (A) | Raildikte H(mm) |
| 800, 1000, 1250, 1600, 2000, 2500, 2900, 3200, 3600, 4000 | 20 |
De stroom komt oerien mei de dikte fan 'e busbar
RDW8HU-6300 Intelligente Universele Stroombrekker (fêst)
| Nominale stroom (A) | Raildikte H(mm) |
| 4000 | 25 |
| 5000~6300 | 30 |
RDW8HU-6300 Intelligente Universele Stroombrekker (Ladetype)
RDW8HU-6300 Intelligente Universele Stroombrekker (Ladetype)